How to specify a cleanroom wall panel

2026-10-22

Most cleanroom wall submittals arrive as a brochure with the word hygienic printed on it. A consultant cannot approve that, and a contractor cannot build from it. Four numbers do the work instead.

One: the fire classification string, not the standard

A document that says tested to EN 13501-1 is incomplete. The classification string is the result: A2-S2,d0,t0 means limited combustibility, limited smoke, no burning droplets. The same standard also produces D-s2,d0 panels.

Ask for the classification report in the project name, and read the string on it.

Two: surface gloss, because glare is a clinical issue

In an operating theatre or an ICU, a glossy wall bounces the surgical light back at the team. A low-gloss surface is not cosmetic — it is fatigue management.

Our medical clean panel runs at a matt finish, measured at roughly 43% lower gloss than the standard specification, which is what removes the hot spot above a bed.

Three: joint width and how it is sealed

A flush panel with a 6 mm open joint is a ledge for dust. Ask for the joint detail in section, and ask what happens at the internal corner, where cleaning actually fails.

Dry-fixed systems should give a sealed, cleanable joint without site silicone, because silicone in a clinical area is a maintenance item that gets missed.

Four: what is inside the wall

A services cavity is the difference between a wall that accepts a socket later and a wall that gets cut open. Ask for cavity depth, and for the panel module that lets a single panel be removed for access.

We build the cavity into the panel, sized for conduit and small ductwork, with panels demountable on a concealed fixing.

PropertyMedical clean panelTiles and paintFRP panel
Fire classificationClass ADepends on substrateVaries
SurfaceMatt, low glareGrout linesGloss, gelcoat
JointSealed, flushGrout, porousSealed or open
Services cavityBuilt inNoneRarely
DemountableYesNoSometimes

FAQ

Does the clean wall panel carry CE marking?

No. CE marking, SGS reports and Korean fire certification apply to our glass-fibre acoustic ceiling range only. The medical clean panel is supplied with fire and surface test reports.

Can it be installed over an existing wall?

Yes — the dry-fixed system is fixed to a levelled substrate, which is why it suits refurbishment of an occupied building.

What about cleanability testing?

Ask any supplier for the specific test method used. A claim of antibacterial without a named standard and named organisms should be treated as marketing.

Send us your wall specification — we will answer clause by clause

Including the clauses we cannot meet.