Cleanroom wall panel systems

A cleanroom is validated by particle counts, but it is built by joints: the seam that opens under pressure, the base that traps disinfectant, the corner nobody can reach with a mop. We make the wall and ceiling panels and supply the floor, and we publish the surface data a validation protocol actually checks.

Class A wall panel A2-S2,d0,t0 ceiling Dry-fix, services in cavity Disinfectant-resistant faces

What the class constrains, and what the panel controls

ISO 14644-1 does not classify products. It classifies a room by the particles it holds at rest and in operation: ISO 5 permits 3,520 particles of 0.5 µm and larger per cubic metre, ISO 7 permits 352,000, ISO 8 permits 3,520,000. In pharmaceutical work these map onto the GMP grades — Grade C areas commonly to ISO 7, Grade D to ISO 8.

No panel delivers a class on its own; air changes, pressure cascade, filtration and human behaviour do the rest. What the panel controls is the part it can ruin: whether the face sheds, whether the joint stays shut at positive pressure, and whether the envelope can be wiped down without going dull or soft.

GMP states it plainly — surfaces smooth, impervious and unbroken, cleanable, resistant to the disinfectants in use. That is a specification for a joint as much as for a face, which is why we draw the junctions before quoting.

Where these panels are specified

  • Aseptic compounding and sterile fill — non-shedding face, sealed grid, coved base, welded floor
  • Oral solid dosage and packaging halls — dust-generating processes, so cleanability beats gloss
  • Quality control and microbiology laboratories — disinfectant resistance and stain resistance on the same face
  • Hospital operating theatres and procedure rooms — Class A wall, demountable ceiling, seamless floor
  • Central sterile supply and pharmacy clean rooms — high humidity, repeated wash-down, aggressive chemistry

Test data

Every value carries its standard. Where the column reads “report on request”, the report is sent with the quotation.

ProductParameterResultTest standard
Medical clean wall panelFire classificationClass AReport on request
Medical clean wall panelSurface glossDiffuse, gloss reduced 42.9%Manufacturer test
Medical clean wall panelDust behaviourNo dust generation, no accumulationManufacturer test
Medical clean wall panelInstallationModular, prefabricated, dry-fixManufacturer test
Glass-fibre resin wall panelFire classificationClass A non-combustibleReport on request
Glass-fibre resin wall panelChemical resistanceDisinfectant-resistant, stain-resistantReport on request
GRP antibacterial ceilingFire classificationA2-S2,d0,t0EN 13501-1
GRP antibacterial ceilingWater absorption0.3%Manufacturer test
GRP antibacterial ceilingAntibacterial / anti-mould99.5% · class I / class 0JIS Z 2801
GRP antibacterial ceilingChemical resistanceResistant to strong acids and alkalisManufacturer test
Homogeneous PVC vinylFire / wear / slipB1 · Class T · R9Report on request
Homogeneous PVC vinylHazardous substancesFree of 19 heavy metals, 60 phthalatesEU 249 screening
No panel is “ISO class certified”. The class belongs to the room and is proven by particle counting to ISO 14644-1 after commissioning. Our claim is narrower: a face that sheds no dust, a joint that stays closed, a surface that survives your disinfectant list.

Panel build-up, dry installation and service access

The wall system is modular and prefabricated, fixed dry. No wet trade behind it means no plaster drying time, no sanding dust and no curing window in front of the pressure test.

Services run inside the panel cavity. Sockets, gas outlets, sensors and alarm points are set out on the drawing and cut before the panel leaves the works, so nobody chases a finished face. The same setting-out drawing is what the validation team measures against.

Panels are cut and labelled by room in installation order. On a suite of fifteen rooms and three ceiling heights, that is the difference between a clean install and a team opening crates to see what is inside.

Junctions that decide the result

  • Wall to ceiling — the ceiling grid closes against the panel head, not against a batten fixed after the fact
  • Wall to floor — coved base formed as part of the floor system, so the cove is welded, not sealed
  • Panel to panel — a joint that stays closed under pressure, and stays cleanable when it does
  • Penetrations — set out on the drawing, cut in the works, sealed to a written detail

Cleaning, disinfection and the humid room

Most cleanroom surface failures are not structural. They are cosmetic in year one and hygienic by year three: a face that chalks under repeated wiping, a gloss that goes patchy where the spray lands, a sealant that softens and holds soil.

The medical clean wall panel is finished low-gloss and diffuse, gloss reduced 42.9% against a standard gloss face. The lower the specular reflection, the less visible the wipe pattern — and the less often a surface is replaced for looking dirty rather than being dirty.

The glass-fibre resin panel is specified where the chemistry is the aggressive part: disinfectant-resistant, stain-resistant, Class A non-combustible. In wash-down and sterile service areas it is usually the wall, with GRP overhead at 0.3% water absorption.

Floors follow the same logic. Homogeneous PVC vinyl is Class T for wear, R9 slip, B1 fire, and free of the 19 heavy metals and 60 phthalate plasticisers screened under EU 249. No waxing, so one fewer chemical in the room.

FAQ

Can you help me hit a specific ISO class?

We can specify the envelope that supports it: non-shedding faces, sealed joints, coved bases, a demountable ceiling for filter access. The class is then proven by particle counting to ISO 14644-1 — the envelope is one variable among several, and we say so.

Will the panels withstand our disinfectant list?

Send the list. Glass-fibre resin is disinfectant- and stain-resistant; GRP ceiling panels resist strong acids and alkalis at 0.3% water absorption. Where a peracetic or chlorine-based regime runs at high frequency, we test against the actual product rather than answer from a datasheet.

What is the minimum order and lead time?

Quoted per project. Panel mix, room count and service penetrations move both figures, so they are confirmed in writing with the quotation.

GRP antibacterial ceiling panelsA2-S2,d0,t0, 0.3% absorptionOpen the range
Hospital wall and ceiling systemsWard, theatre, ICUOpen the solution

Send the room data sheet and the disinfectant list

A panel schedule with joint details and the report behind each surface claim.

Request the specification pack